Festo Контроллер позиционирования CPX-CMAX User Manual
Page 278
5. Parameter
5−90
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
Limit values
PNU
PNU: 1173
Index: 1
Max index: 14
Class: Array
Data type: int32
Values
See description of the respective index.
Default: 0
Minimum: −
Maximum: −
Information on the limits for the positioning stroke carried out last, see section3.1.8.
Index
Value
Unit
1
Status: see below
−
2
Start position (actual value)
Position (index 1)
3
Target position
Position (index 1)
4
Setpoint acceleration
Acceleration (index 7)
5
Maximum acceleration value
Acceleration (index 7)
6
Setpoint deceleration
Acceleration (index 7)
7
Maximum deceleration value
Acceleration (index 7)
8
Setpoint speed
Speed (index 6)
9
Maximum speed value
Speed (index 6)
10
Setpoint force
Force (index 3)
11
Maximum force value
Force (index 3)
12
Force ramp setpoint
Force ramp (index 8)
13
Maximum force ramp value
Force ramp (index 8)
14
Starting force (last setpoint)
Force (index 3)
The status word is used as a handshake between CMAX and FCT. As soon as the bit 0 is set by the
controller, the data are no longer overwritten. In this way the FCT can consistently read the data.
After reading, FCT writes a 0 into the status word as confirmation, and the controller updates the
values. The status word (index 1) may be written by the FCT without higher−order controller. It is also
not necessary to enter a password.
Bit
Status information
0
= 1:
New values are now available
1
= 1:
Acceleration was limited
2
= 1:
Deceleration was limited
3
= 1:
Speed was limited
4
= 1:
Force setpoint value was limited
5
= 1:
Force ramp was limited
6 ... 15
Reserved
16 ... 23 In case of Record select mode: Number of the record executed last.
24
= 0:
Record select mode / = 1: Direct mode
25
= 0:
Positions setpoint/ = 1: Force setpoint value
26
= 0:
Unassigned profile / = 1: Auto−profile
27 ... .31 Reserved
ý
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
o
After writing, controller recalculation is carried out.