5. Parameter
5−43
Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH
5.4.5
Record list
Requested record number
PNU
PNU: 400
Index: 1
Max index: 3
Class: Struct
Data type: int32
Values
Without unit
Default: 0
Minimum: 0
Maximum: 64
The record number that was accepted with the last starting edge.
If no record was started yet, the value will be 0 (no permissible record number).
ý
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
o
After writing, controller recalculation is carried out.
Actual record number
PNU
PNU: 400
Index: 2
Max index: 3
Class: Struct
Data type: int32
Values
Without unit
Default: 0
Minimum: 0
Maximum: 64
The number of the record executed last.
If no record was executed yet, the value will be 0. This is no permissible record number.
ý
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
o
After writing, controller recalculation is carried out.
Record status byte
PNU
PNU: 400
Index: 3
Max index: 3
Class: Struct
Data type: bitarray
Values
Default:
0000 0000 0000 0000 0000 0000 0000 0000
Write:
−
Record status byte (RSB): contains a feedback code that is transferred to the input data.
In accordance with FHPP, only bits 0 ... 7 are defined. Bits 8 ... 31 are always 0. For a description of
the bits, see section 2.2.3.
ý
The parameter value cannot be changed.
o
Writing permissible only in commissioning/parametrising mode with disabled controller.
o
This parameter can be written by FCT without higher−order controller.
o
After writing, controller recalculation is carried out.