4. Troubleshooting (PROFIBUS DP)

4.2.3.5 Network Configuration and Specifications

(1) Maximum Cable Length

Check that the cables used on the network meet the following specifications.

Baud Rates

Max. Cable Length

12 Mbps

6 Mbps
3 Mbps

1500 kbps

500 kbps

187.5 kbps
93.75 kbps

19.2 kbps

9.6 kbps

100 m
100 m
100 m
200 m
400 m

1000 m
1200 m
1200 m
1200 m

(2) Terminating Resistor

Ensure that two terminating resistors are connected to both ends of the network.
The terminating resistor should be connected as shown below.

VP (6)

390

RxD/TxD-P (3)

220

RxD/TxD-N (8)

390

DGND (5)

Data Line B

Data Line A

(3) Cable

The cables should meet the PROFIBUS specifications.

Item Property

Impedance

135 to 165

Capacity

< 30 pf/m

Loop resistance

110

Ω/km

Wire diameter

0.64 mm

Core cross-section

> 0.34mm

2

Fieldbus I/O Rev.6