4. Troubleshooting (PROFIBUS DP)
4.2.2.1.2 Slave: Data Link Error
MS
NS
Master LED Condition
Light OFF
Red Light Blinking
Absent Slave LED Condition
(Data link error)
Light OFF
Red Light ON
♦ Process Flowchart
Replace the unit.
3
No Problem
Check
Check the following:
- Unconnected terminating resistor
- Unconnected or loose connector/signal wire
- Cable disconnection
Finish
No Change
No Change
The trouble unit is not found.
Rarely
Problem exists. (Fix it.)
No change
Immediately
The unit is not found.
The unit is found.
Yes
The problem is fixed.
The problem is fixed.
No
No problem
See 4.2.3.1 and 4.2.3.2.
See 4.2.3.3.
No change
Check for noise influence.
Divide the network and
find the trouble unit.
Does an error occur immediately?
Normal Communication?
Consult the PROFIBUS manufacturer.
Replace moving cable.
(Replace deteriorated cable).
Fieldbus I/O Rev.6
119
- C8230 (29 pages)
- 400 (38 pages)
- 400 (148 pages)
- 600 (135 pages)
- 640 (45 pages)
- 700 (10 pages)
- 850 (147 pages)
- 1520 (40 pages)
- C82314 (71 pages)
- RS-485 (2 pages)
- 6200A (97 pages)
- C82307 (37 pages)
- UB E02 (86 pages)
- 440 (240 pages)
- 440 (212 pages)
- 660 (92 pages)
- 5000 (176 pages)
- 5000 (154 pages)
- 9000 (68 pages)
- ARM.POWERED ARM720T (224 pages)
- SD-DSPUSBB (2 pages)
- CMD-2260 (18 pages)
- C823301 (17 pages)
- S1C6200A (98 pages)
- 33+ (10 pages)
- FEH300b (46 pages)
- SED 1520 Series (40 pages)
- Serial Interface GQ-3500 (13 pages)
- ETX-945 (39 pages)
- Photo EX (35 pages)
- C82364 (279 pages)
- 214D-1 (57 pages)
- Connect-It SD-DSWIFIB (2 pages)
- ACTIONPC 7000 (10 pages)
- S5U1C63000H2 (35 pages)
- C824 (4 pages)
- C82069* (46 pages)
- 80211b (68 pages)
- C82312 (13 pages)
- S5U1C17801T1100 (60 pages)
- C82324* (57 pages)
- C82372 (22 pages)
- C82315 (48 pages)
- P07303 (36 pages)