beautypg.com

Epson EM07ZS1647F User Manual

Page 143

background image

4. Troubleshooting (PROFIBUS DP)

♦ Process Flowchart

Normal

See 4.2.3.2.

Turn OFF all units.

Normal

Resistance: over 120

Measure
resistance at
connectors
with tester.

Resistance: under 100

Problem exists.
(Add terminating resistors.)

Out of 100 to 120

Ω (Error)

Yes

Other

Approx.

220

10 to 100

Under 10

No

(1) Unconnected or loose connector
(2) Cable disconnection, etc.

(1) Three

or

more

terminating resistors

(2) Wrong

terminating

resistors, etc.

Short circuit

between signal

wires

Check for cable laying.

Find the trouble point.

Check for connection

of terminating resistors.

Check that

terminating resistors

are connected.

Measure resistance

with tester.

100 to 120

Remove one terminating

resistor on either side.

Check for short

circuit between

signal wires.

Fieldbus I/O Rev.6

131