4. Troubleshooting (PROFIBUS DP)

Countermeasure 1: Improve FG.

Peel the cable covering and

secure the cable with FG clamps.

Grounding Screw

Isoelectric Line

Grounding Screw

Slave Device

Slave Device

Countermeasure 2: Disconnect the FG wire to isolate it from the ground.

When noise intrudes the ground line because a noise source such as an inverter is
installed near the grounding point, disconnect the shield wire of the signal cable and
isolate it from the ground to restrain noise intrusion.

Disconnect the grounding wire.

♦ Induced noise via communication cable

Separate the PROFIBUS DP signal wire from the other wires (especially power wires).

* Separate the signal wire from the power wires 300 mm or more.

Light electrical cable
Communication cable

Control cable

Power cable

Signal wire

PLC input/output wire

PLC power wire

Control circuit wire

Power wire

Suspended ducts

Floor ducts

1

2

1

2

1 2

1 Signal wire

PLC input/output wire

2 Power wire

300 mm

or more

300 mm

or more

Conduit

During site inspection, bypass the wire that is possibly affected by induced noise with other
cables and then lay the cables. Establish the communication under no induced noise
condition and verify whether an error occurs.

Fieldbus I/O Rev.6