beautypg.com

Epson EM07ZS1647F User Manual

Page 111

background image

4. Troubleshooting (DeviceNet)

♦ Process Flowchart

Check that

terminating resistors

are connected.

Measure resistance

with tester.

50 to 70

Normal

See 4.1.3.2.

Turn OFF communications power supply.

Normal

Resistance: over 70

Remove one terminating

resistor on either side.

Measure

resistance at

connectors and

branch taps with

tester.

Resistance: under 50

Problem exists.
(Add terminating resistors.)

Out of 50 to 70

Ω (Error)

Yes

Other

Approx.

120

10 to 50

Under 10

No

(1) Unconnected or loose connector
(2) Cable disconnection, etc.

(1)

Three or more

terminating resistors

(2) Wrong

terminating

resistors, etc.

Short circuit
between signal

wires

Check for cable laying.

Find the trouble point.

Check for connection

with terminating resistors

and branch taps.

Check for short

circuit between

signal wires.

Fieldbus I/O Rev.6

99