Technical Data
SMA Solar Technology AG
90
SB20HF-30HF-IA-en-32
Installation Manual
Protective devices
General Data
DC reverse polarity protection
Short‑circuit diode
Input‑side disconnection device
Electronic Solar Switch
DC overvoltage protection
Thermally monitored varistors
AC short‑circuit current capability
Current control
Grid monitoring
SMA Grid Guard 3
Maximum permissible fuse protection
25 A
Ground fault monitoring
Insulation monitoring: R
iso
> 1 M Ω
Galvanic isolation
Available
Width x height x depth with
Electronic Solar Switch
348 mm x 580 mm x 145 mm
Weight
17 kg
Length x width x height of packaging
600 mm x 400 mm x 450 mm
Transport weight
21 kg
Climatic category according to IEC 60721‑2‑1
4K4H
Operating temperature range
− 25°C … +60°C
Maximum permissible value for relative humidity,
non‑condensing
100%
Maximum operating altitude above mean sea
level
3 000 m
Noise emission (typical)
≤ 38 dB(A)
Power loss in night operation
< 1 W
Topology
HF transformer
Cooling concept
OptiCool: temperature‑controlled fan
Fan connection
Designed for safe disconnection
in accordance with DIN EN 50178:1998‑04
Degree of protection according to IEC 60529
IP65
Protection class (according to IEC 62103)
I