5.3.4 Setting the Country Standard and Language using the Rotary
Switch
1. Open the Quick Module, as described in section 5.3.3 "Opening the Quick Module"
2. Set the arrows on both left rotary switches
(A and B) to the desired positions using a
screwdriver (see table in section 5.3.2 "Checking
the Country Standard" (page 24)). For this
purpose, use a screwdriver with a blade width of
2.5 mm.
☑ The country standard and the language are set.
5.3.5 Communication via Bluetooth
Communication via Bluetooth with a communication product is activated as standard. Networking via
Bluetooth with other inverters is deactivated ex works.
The following configuration settings are possible via a rotary switch (switch C):
In order to restrict communication via Bluetooth between the inverters of your plant and those of
neighboring plants, you can assign an individual NetID to the inverters of your plant (switch position
2 ... F). However, this is only necessary if neighboring plants are within a radius of 500 m.
So that all inverters in your PV plant are detected by your communication product, all inverters must
have the same NetID.
Jumper for English
You can also set the language to English by
means of a jumper (e.g. for service purposes).
• To do this, place the jumper onto both
left pins as shown in the diagram on the
right.
Switch position (NetID)
Setting
0
off
1
Communication via Bluetooth with communication product possible,
no networking with other inverters (default settings)
2 ... F