3 abortion of the self‑test, Abortion of the self‑test – SMA SB 2000HF-30 Installation User Manual
Page 56
Commissioning
SMA Solar Technology AG
56
SB20HF-30HF-IA-en-32
Installation Manual
Minimum frequency
After the maximum frequency test, the minimum frequency
test takes place and the inverter shows the adjacent
display message for 5 seconds.
During the test sequence, the frequency limit applied is
shown in the display of the inverter. The frequency limit is
increased successively until the shut‑down threshold is
reached and the inverter disconnects from the power
distribution grid.
Once the inverter has disconnected from the power distribution grid, the display successively shows
each of the following values one after the other for 10 seconds:
• Disconnection value,
• Calibration value,
• Reaction time.
The change between the first and second display takes places every 2.5 seconds.
7.3.3 Abortion of the Self‑Test
If, during the self‑test, an unexpected disconnection requirement occurs, the self‑test is aborted.
The same applies if the DC voltage is so low that the feed‑in cannot be continued.
• The inverter then shows the adjacent display
message for 10 seconds.
• Restart the self‑test as described in the following