beautypg.com

SMA SB 2000HF-30 Installation User Manual

Page 73

background image

SMA Solar Technology AG

Troubleshooting

Installation Manual

SB20HF-30HF-IA-en-32

73

☑ A ground fault exists if the measured voltages are stable and the sum of the voltages from

the positive pole to the ground potential and from the negative pole to the ground potential
of a string is approximately equal to the voltage between the positive and negative poles.

Location of the ground fault

The approximate position of the ground fault can be determined from the ratio of the measured
voltages between the positive pole against ground potential (PE) and the negative pole against
ground potential (PE).
Example:

In this case, the ground fault is between the second and third PV modules.

☑ The ground fault check is finished.

Result

Measure

☑ You have found a ground fault.

• The installer of the PV array must remedy

the ground fault in the affected string. You
can determine the location of the ground
fault as described below.

• Do not reconnect the faulty string.
• Recommission the inverter as described in

section 7 "Commissioning" (page 49).

☑ You have found no ground fault.

It is likely that one of the thermally monitored
varistors is defective.

• Check the function of the varistors as

described in section 11.2 "Checking the
Function of the Varistors" (page 74).

This manual is related to the following products: