SMA SB 2000HF-30 Installation User Manual
Page 71
SMA Solar Technology AG
Messages
Installation Manual
SB20HF-30HF-IA-en-32
71
74
< Varistor defective >
• Check the varistors as described in
section 11.2 "Checking the Function
of the Varistors" (page 74).
75
< Fan fault >
< Clean fan >
• Check the heat dissipation as
described in section 9.2 "Checking
the Heat Dissipation" (page 61).
77
< Self diagnosis >
< Interference device >
• Contact the SMA Service Line (see
section 15 "Contact" (page 94)).
80
< Derating occurred >
The power supplied by the inverter was
reduced to below the nominal power due
to high temperature for more than
10 minutes.
If this event occurs frequently:
• Ensure sufficient ventilation.
• Check the heat dissipation as
described in section 9.2 "Checking
the Heat Dissipation" (page 61).
81
< Comm. disturbed >
A fault has occurred in the internal
communication of the inverter. However,
the inverter continues feeding into the grid.
If this event occurs frequently:
• Contact the SMA Service Line (see
section 15 "Contact" (page 94)).
90
< Inst. code invalid >
The SMA Grid Guard Code entered
(personal installer password) is invalid.
• A valid SMA Grid Guard Code has
been entered.
< Grid param. locked >
The current country data set is locked.
• Enter the valid SMA Grid Guard
Code for changing the country data
set.
< Abort self‑test >
• Contact the SMA Service Line (see
section 15 "Contact" (page 94)).
< Changing grid param. not possible >
• The selected rotary switch setting for
the country configuration is not
programmed.
• The parameters to be changed are
protected.
< Ensure DC supply >
The DC voltage for the writing
procedure is not sufficient.
• Check the setting of the rotary switch
(see section 5.3.2 "Checking the
Country Standard" (page 24)).
• Enter the SMA Grid Guard Code.
• Ensure that sufficient DC voltage is
available.
Event no. Display message and cause
Corrective measures