Messages

Installation Manual

SB20HF-30HF-IA-en-32

69

35

< Insulation resist. >

< Check generator >

The inverter has detected a ground fault in
the PV array. However, the inverter
continues feeding into the grid.

• Check the strings for ground faults as

described in section 11.1 "Checking
the PV Array for Ground Faults"
(page 72).

• The installer of the PV array must

remedy the ground faults before you
re‑connect the affected string.

< Ground fuse fault >

< Check ground fuse >

The inverter has detected a ground voltage
in the grounding path.

• Check the ground fuse as described

in the installation manual of the
SMA Plug-in Grounding.

• Check the strings for ground faults as

described in section 11.1 "Checking
the PV Array for Ground Faults"
(page 72).

38

< DC overcurrent >

< Check generator >

The inverter switches off due to an
overcurrent on the DC side.

If this event occurs frequently:

• Check the design and the wiring of

the PV array.

39

< Waiting for DC start conditions >
< Start cond. not met >
The feed‑in power or feed‑in voltage of the
PV modules is insufficient for feeding into
the power distribution grid.

• Wait for more sunlight.
• If this event recurs even when the

amount of sunlight is average, check
the design of your PV plant and make
sure the PV array is wired properly.

42

< Wrong earthing type; check earthing set >
The SMA Plug‑in Grounding polarity does
not correspond to the polarity set in the
inverter.

• Correct the grounding type as

described in the installation manual
for the SMA Plug‑in Grounding.

60 ‑ 64

< Self diagnosis >
< Interference device >

• Contact the SMA Service Line (see

section 15 "Contact" (page 94)).

65

< Self diagnosis >
< Overtemperature >
The inverter switches off due to too high
temperature

• Ensure sufficient ventilation.
• Check the heat dissipation as

described in section 9.2 "Checking
the Heat Dissipation" (page 61).

66

< Self diagnosis >
< Overload >

• Contact the SMA Service Line (see

section 15 "Contact" (page 94)).

67

< Comm. disturbed >
A fault has occurred in the internal
communication of the inverter. However,
the inverter continues feeding into the grid.

If this event occurs frequently:

• Contact the SMA Service Line (see

section 15 "Contact" (page 94)).

Event no. Display message and cause

Corrective measures