beautypg.com

SMA SB 2000HF-30 Installation User Manual

Page 16

background image

Assembly

SMA Solar Technology AG

16

SB20HF-30HF-IA-en-32

Installation Manual

• Mount vertically or tilted backwards at a maximum angle of 30°.
• The connection area must point downward.
• Never mount the device with a forward tilt.
• Never install the device with a sideways tilt.
• Do not mount horizontally.
• Mount at eye level to allow operating states to be read at all times.
• The ambient temperature should be below +40°C to ensure optimal operation.
• Do not expose the inverter to direct solar irradiation as this can cause excessive heating and

thus power reduction.

• In living areas, do not mount the unit on plasterboard walls or similar to avoid audible vibrations.

When in use, the inverter emits noises which may be perceived as a nuisance in a living area.

• Observe the minimum clearances to walls, other

inverters, or objects as shown in the diagram in
order to ensure sufficient heat dissipation and
sufficient space for removing the Electronic Solar
Switch.

Multiple inverters installed in areas with high ambient temperatures
If necessary, increase the clearances between the individual inverters. In addition, make
sure there is enough fresh‑air supply to ensure sufficient cooling of the inverters.

This manual is related to the following products: