6.3 Connection to the Power Distribution Grid (AC)

6.3.1 Conditions for the AC Connection

Cable design

Use "Sunny Design" version 2.0 or higher for the dimensioning of the conductor cross‑sectional areas
(see "Sunny Design" design program at www.SMA.de/en).

Cable Requirements

Connection requirements of the grid operator
Always observe the connection requirements of your grid operator.

Position

Designation

Value

A

External diameter

6 mm ... 14 mm

B

Stripping length

30 mm

C

Cable cross‑section

2.5 mm² ... 4 mm²

D

Length of insulation to be stripped off

8 mm

D

B

A

C