Page 24
The Communication Module (Quick Module)
SMA Solar Technology AG
24
SB20HF-30HF-IA-en-32
Installation Manual
5.3.2 Checking the Country Standard
The switch position 0 / 0 indicates the delivered state. If you have ordered the inverter with specific
country settings, they will have already been preset at the factory via a communication product. In this
case, you will not be able to recognize the setting by the switch position. If changes are made via the
rotary switches or via a communication product, the default grid parameters are overwritten. They
cannot be restored, and must be re‑entered via a communication product. The display language can
be changed at any time using the rotary switches, independently of the grid parameters. This means
that the default grid parameters remain unchanged, but the display messages are shown in the set
language. For devices ordered without any specified country of installation, the standard setting is
"VDE0126‑1‑1" and the language "Deutsch" (German).
Changes will be accepted immediately after switching the miniature circuit‑breaker on. If an
unprogrammed switch setting is selected, the inverter issues an error message on the display and the
last valid setting is retained.
Check whether the inverter is set to the installation country.
Before commissioning:
• Check that the country setting of the inverter is correct by comparing the additional sheet
provided with the default settings of the inverter.
After commissioning:
• Check that the country standard is correct on the basis of the display message during
(re‑)commissioning (see section 7.2 "Display Messages During the Startup Phase" (page 51)).
or
• Check that the country standard is correct using the "SMA grid guard" measuring channel via
a communication product.
The operating parameters define which parameter set refers to which setting. The parameters can be
read out using a communication product. A detailed description of the parameters and measured
values for the inverter is available in the download area at www.SMA.de/en in the
"Technical Description" category for the respective inverter.
Display language
Once you have set the country standard, you can always set the display language later
using rotary switch B. However, you have to then set rotary switch A to "0" in order to keep
the country data set.
(A) (B) Country data set
Display language
Grid Guard
protection
Country
0
0
Delivery state
Delivery state
Dependent on
parameter set
Dependent on
parameter set
0
1
Retained
English
Dependent on
parameter set
Dependent on
parameter set
0
2
Retained
German
Dependent on
parameter set
Dependent on
parameter set