beautypg.com

SMA SI 4548-US User Manual

Page 73

background image

SMA America, LLC

8  Commissioning

Operating Manual

SI4548-6048-US-BE-en-20

73

Make sure the insulated conductors have the correct polarity.

– BatCur+ to terminal 1
– BatCur– to terminal 2

9. Start the Sunny Island (see Section 9.1 "Switching On", page 74).

10. Check the current direction: "120.06 TotBatCur"

Current direction: Discharging the battery

• No generator/utility grid connected
• Loads are being supplied

The measured value of the battery current is positive.

Current direction: Charging the battery

• Generator/utility grid connected
• Loads are not/marginally supplied
• Battery is being charged

The measured value of the battery current is negative.

This manual is related to the following products: