beautypg.com

8 aux category – SMA SI 4548-US User Manual

Page 216

background image

20  Troubleshooting

SMA America, LLC

216

SI4548-6048-US-BE-en-20

Operating Manual

20.8.8 AUX Category

Display no.

Level

Description

F801

4

Plausibility check of contactors in a Multicluster Box failed

W804

1

Grid operation not possible

W805

1

Generator operation not possible

F806

4

Multicluster Box settings do not match software settings.

W807

1

No valid line voltage for requested grid operation

W808

1

Error Q4 contactor

F809

4

Error Q10 contactor (load shedding)

F810

4

Error in 15 V supply of the Multicluster Box

F811

4

Error in 24 V supply of the Multicluster Box

W815

1

Error Q5 contactor

F816

2

Error Q7 contactor

F817

4

Error Q9 contactor

F818

4

A phase is missing, Multicluster Box goes into "Failure" status

W824

1

Error Q4 contactor

W851

1

Battery reversely connected or short circuit on Sunny Island Charger 1

W852

1

Battery overvoltage Sunny Island Charger 1

W853

1

Overvoltage PV array Sunny Island Charger 1

W854

1

No PV voltage or short circuit on Sunny Island Charger 1

W855

1

Sensor error (or undertemperature) on Sunny Island Charger 1

W856

1

Overtemperature Sunny Island Charger 1

W857

1

No communication with Sunny Island Charger 1 for more than 24 h

W861

1

Battery reversely connected or short circuit on Sunny Island Charger 2

W862

1

Battery overvoltage Sunny Island Charger 2

W863

1

Overvoltage PV array Sunny Island Charger 2

W864

1

No PV voltage or short circuit on Sunny Island Charger 2

W865

1

Sensor error (or undertemperature) on Sunny Island Charger 2

W866

1

Overtemperature Sunny Island Charger 2

W867

1

No communication with Sunny Island Charger 2 for more than 24 h

W871

1

Battery reversely connected or short circuit on Sunny Island Charger 3

W872

1

Battery overvoltage Sunny Island Charger 3

W873

1

Overvoltage PV array Sunny Island Charger 3

This manual is related to the following products: