SMA SI 4548-US User Manual
Page 140
15 Relays
SMA America, LLC
140
SI4548-6048-US-BE-en-20
Operating Manual
ExtVfOk
External voltage and
frequency OK
External voltage and frequency are within the valid
range for connection.
GdOn
Utility grid
Relay switching when utility grid is available and
connected.
Error
Error
Sunny Island has a fault; in case of fault, contact is
open (relay is deactivated).
If the autostart is activated, the error status will be
left within 15 s and restart triggered. If the start is
unsuccessful this procedure will be repeated until
the autostart counter has expired.
Warn
Warning
The Sunny Island has warning pending. If the
warning disappears, the "Warning" state is quit.
When a warning disappears depends on the type
of warning.
Run
Run
Sunny Island is in operation, contact is closed
(relay is activated) if the device is running in
inverter operation.
BatFan
Battery Fan
Relay is used for automatic battery room ventilation
(switching the fan).
The "BatFan" function is responsible for the
ventilation of the battery room and provides
ventilation of the room in the event of battery
gassing.
AcdCir
Acid Circulation
Relay is used for automatic acid circulation
(switching the electrolyte pump)
The acid circulation enables mixing of the acid and
thus reduces acid stratification in the battery.
MccBatFan
Multicluster battery fan
Relay is used for automatic battery room ventilation
(switching the fan).
"MccBatFan" is the request from the master of the
main cluster that is transmitted to a master of an
extension cluster in order to use its relay for the
battery room ventilation.
Function/
Setting
Meaning
Function description