20  Troubleshooting

Operating Manual

SI4548-6048-US-BE-en-20

215

W744

1

Internal CAN communication of slave 1 is interrupted

W745

1

Internal CAN communication of slave 2 is interrupted

W746

1

Internal CAN communication of slave 3 is interrupted

W747

1

Short circuit or cable break on transformer temperature sensor slave 1

W748

1

Short circuit or cable break on transformer temperature sensor slave 2

W749

1

Short circuit or cable break on transformer temperature sensor slave 3

W750

1

Short circuit or cable break on heat sink temperature sensor slave 1

W751

1

Short circuit or cable break on heat sink temperature sensor slave 2

W752

1

Short circuit or cable break on heat sink temperature sensor slave 3

W753

1

Invalid system time

F754

2

Communication with Multicluster Box interrupted

W755

1

Battery-preservation mode 1 (LBM)

W756

1

Battery-preservation mode 2 (LBM)

W757

1

Battery-preservation mode 3 (LBM)

F758

2

No output voltage measured from the main cluster

W759

1

No output voltage measured from slave 1 of main cluster

W760

1

No output voltage measured from slave 2 of main cluster

W761

1

No output voltage measured from slave 3 of main cluster

F781

4

Error at a slave which leads to shutdown of the system (for the
"RunMod" function)

F782

4

Failure of the grid monitoring

F783

2

Slave does not receive a Syncpuls

W784

1

Slave does not receive a Syncpuls Slave 1

W785

1

Slave does not receive a Syncpuls Slave 2

W786

1

Slave does not receive a Syncpuls Slave 3

W791

1

DSP reset detected on slave 1

W792

1

DSP reset detected on slave 2

W793

1

DSP reset detected on slave 3

W797

1

Failure of the grid monitoring slave 1

W798

1

Failure of the grid monitoring slave 2

W799

1

Failure of the grid monitoring slave 3

Display no.

Level

Description