233# Grid Start
15
GdAlSns
AI sensitivity
Low
Low
Normal
Medium
Medium
Normal
Normal
High
High
37
GdVtgIncProEna Voltage increase
protection
Disable
Disable
Disable
Enable
Enable
38
GdVtgIncPro
Limit for voltage
increase protection
132 V
41
GdSocEna
Activate the grid
request based on SOC
Disable
Disable
Disable
Enable
Enable
42
GdPwrEna
Activate the grid
request based on
power
Disable
Disable
Disable
Enable
Enable
No. Name
Description
Value
Explanation
Default
value
01
GdSocTm1Str
SOC limit for switching
on utility grid for time 1
40%
02
GdSocTm1Stp
SOC limit for switching
off the utility grid for time
1
80%
03
GdSocTm2Str
SOC limit for switching
on utility grid for time 2
40%
04
GdSocTm2Stp
SOC limit for switching
off the utility grid for time
2
80%
05
GdTm1Str
Time 1 for grid request in
hours, minutes and
seconds
Start: time 1, end: time 2
06
GdTm2Str
Time 2 for grid request in
hours, minutes and
seconds
Start: time 2, end: time 1