SMA SI 4548-US User Manual
Page 168
19 Parameter Lists
SMA America, LLC
168
SI4548-6048-US-BE-en-20
Operating Manual
#223 Battery Protection
07
ChrgVtgBoost
Cell voltage
setpoint for normal
charge
2.2 V to 2.7 V
VRLA
2.40 V
FLA
2.55 V
1.5 V to 1.8 V
NiCd
1.65 V
08
ChrgVtgFul
Cell voltage
setpoint for full
charge
2.3 V to 2.7 V
VRLA
2.40 V
FLA
2.50 V
1.5 V to 1.8 V
NiCd
1.65 V
09
ChrgVtgEqu
Cell voltage
setpoint for
equalization
charge
2.3 V to 2.7 V
VRLA
2.40 V
FLA
2.50 V
1.5 V to 1.8 V
NiCd
1.65 V
10
ChrgVtgFlo
Cell voltage
setpoint for float
charge
2.2 V to 2.4 V
VRLA
2.25 V
FLA
2.25 V
1.4 V to 1.6 V
NiCd
1.55 V
11
BatTmpCps
Battery
temperature
compensation
0 mV/C° to
10 mV /°C
VRLA
4.0 mV/
°C
FLA
4.0 mV/
°C
NiCd
0 mV/
°C
12
AutoEquChrgEn
a
Automatic
equalization
charge
Disable
Disable
Enable
Enable
Enable
No. Name
Description
Value
Default value
01
BatPro1TmStr
Starting time of the
battery-preservation
mode (level 1)
22:00:00
02
BatPro1TmStp
End time of the
battery-preservation
mode (level 1)
06:00:00
03
BatPro2TmStr
Starting time of the
battery-preservation
mode (level 2)
17:00:00
No. Name
Description
Value
Explanation
Default
value