3 generator operation, 4 manual generator operation, Tor (see section 14.1.4 "manual generator – SMA SI 4548-US User Manual
Page 121
SMA America, LLC
14 Connecting External Sources
Operating Manual
SI4548-6048-US-BE-en-20
121
If the generator is started manually in this operating mode, the Sunny Island detects the running
generator and connects it once the warm-up time has expired. If you stop the generator externally,
this is detected, the generator disconnected and the stand-alone grid is still supplied.
14.1.3 Generator Operation
The Sunny Island allows automatic operation (depending on the state of charge or load) (see
Section 14.1.5 "Automatic Generator Operation", page 122). In addition, manual operation is also
possible.
14.1.4 Manual Generator Operation
The manual operating modes for the generator management are tripped using the parameter
"540.01 GnManStr". Here, a distinction is made between the following operating modes:
Generator request
If the generator is running after being externally started and a generator request occurs, the
GnReq signal is disabled until the generator is externally stopped again and the stop time has
expired.
Auto:
In this operating mode, the generator is automatically started due to the settings.
This includes the start via the state of charge or the load power or by the request for
a manual equalization charge.
("520.01 ChrgSelMan" = Start).
Stop:
The generator is manually stopped. The current generator request is canceled –
immediate disconnection from generator and change to lock state. Once the lockout
time has ended, the generator switches into automatic operation.
Start:
Manual generator start – the generator runs "continuously" until stopped. The
generator can only be manually stopped.