SMA America, LLC
19 Parameter Lists
Operating Manual
SI4548-6048-US-BE-en-20
171
232# Grid Control
05
ExtSrc
generator and grid
operating mode
PvOnly
PV only
PvOnly
Gen
Generator
Grid
Utility grid
GenGrid
Generator/
utility grid
12
ChpEna
Combined heat and
power plant
Disable
Deactivated
Disable
Enable
Activated
No. Name
Description
Value
Explanation
Default
value
01
GdVtgMin
Minimum grid voltage
105.6 V
02
GdVtgMax
Maximum grid voltage
132 V
03
GdCurNom
Nominal grid current
30 A
04
GdFrqNom
Nominal grid
frequency
60 Hz
05
GdFrqMin
Minimum power
frequency
59.3 Hz
06
GdFrqMax
Maximum power
frequency
60.5 Hz
07
GdVldTm
Minimum time required
for grid (voltage and
frequency) to be within
permissible range for
connection
300 sec
08
GdMod
Grid interface
GridCharge
Charging on the
utility grid
GdFeed
GridFeed
Charge and
feedback on the
utility grid
09
GdRvPwr
Permissible grid reverse
power (active power)
0 W to 5,000 W
100 W
10
GdRvTm
Permissible time for
grid reverse power
0 sec to 60 sec
5 sec
No. Name
Description
Value
Explanation
Default
value