SMA SI 4548-US User Manual
Page 181
SMA America, LLC
19 Parameter Lists
Operating Manual
SI4548-6048-US-BE-en-20
181
242# Relay Load
07
ExtPwrDerMinT
m
Minimum time of
external power
reduction
0 min to
600 min
10 min
08
ExtPwrDerDltVtg Differential voltage
of external power
reduction
0 V to 0.4 V
0.15 V
No. Name
Description
Value
Explanation
Default
value
01
Lod1SocTm1Str SOC limit for load
shedding 1 start for t1
30%
02
Lod1SocTm1Stp SOC limit for load
shedding 1 stop for t1
50%
03
Lod1SocTm2Str SOC limit for load
shedding 1 start for t2
30%
04
Lod1SocTm2Stp SOC limit for load
shedding 1 stop for t2
50%
05
Lod1Tm1Str
Time 1 for Loadshed 1
in hours, minutes and
seconds
Start: time 1, end: time
2
06
Lod1Tm2Str
Time 2 for Loadshed 1
in hours, minutes and
seconds
Start: time 2, end: time
1
07
Lod2SocTm1Str SOC limit for load
shedding 2 start for t1
30%
08
Lod2SocTm1Stp SOC limit for load
shedding 1 stop for t2
50%
09
Lod2SocTm2Str SOC limit for load
shedding 2 start for t2
30%
10
Lod2SocTm2Stp SOC limit for load
shedding 2 stop for t2
50%
No. Name
Description
Value
Explanation
Default
value