5 display of failures and events, 6 events, 1 category inv – SMA SI 4548-US User Manual
Page 204

20 Troubleshooting
SMA America, LLC
204
SI4548-6048-US-BE-en-20
Operating Manual
20.4 Handling of Pending Errors during the Booting Procedure
During the booting procedure, all pending failures are generally confirmed without an entry being
made in the history. This way, after the booting procedure, a failure that is still pending will be
reentered, or if the system detects that this failure has disappeared, it is entered as no longer being
present.
20.5 Display of Failures and Events
Each failure and each event have a unique three-digit display number that is created according to the
parameter/measuring value assignment. The events and failures have the identical numerical range:
• 1xx ‒ INV ‒ Inverter
• 2xx ‒ BAT ‒ Battery
• 3xx ‒ EXT ‒ External
• 4xx ‒ GEN ‒ Generator
• 5xx ‒ GRD ‒ Grid
• 6xx ‒ RLY ‒ Relay
• 7xx ‒ SYS ‒ System
• 8xx ‒ AUX ‒ External devices and components
20.6 Events
The meanings of the events displayed by the Sunny Island are described in the following table:
20.6.1 Category INV
No comparison between master and slave
The error and event memory are not compared between the master and slaves. The errors of
the slave device are acknowledged when the Sunny Island system is restarted.
Meaning of abbreviations
"F" indicates a failure, "W" a warning and "E" an event.
In the event of a failure, and provided it is recorded, "!" is displayed for a failure that has
occurred and "C" is displayed for a failure that has stopped.
Display no.
Description
E101
Waiting mode
E102
Startup process
E103
Operation
E104
Operating on the generator (at external input)
E105
Operation on utility grid (at external input)
E106
Feeding-in grid operation (at external input)