beautypg.com

SMA SI 4548-US User Manual

Page 32

background image

4  Mounting

SMA America, LLC

32

SI4548-6048-US-BE-en-20

Operating Manual

• Mount the Sunny Island in such a way that the display is at eye level in order to allow the

operating state to be read at all times.

• Mount vertically or tilted backwards by max. 45°.
• Never mount the device with a forward tilt.
• Do not mount in a horizontal position.
• The connection area must not point upwards.
• The room air can have a humidity of up to 100%, but this must not be condensing.

• In a living area, do not mount the unit on

plasterboard walls, etc. in order to avoid audible
vibrations.
The Sunny Island can make noises when in use
which can be considered a nuisance when installed
in a living area.

• Maintain the minimum distances to walls, other

devices and objects as represented in the
illustration.
In order to maintain sufficient ventilation, when
installing the device a minimum clearance of 12 in
(30 cm) at the sides and top must be maintained.
Operation and reading are made easier by
installing the Sunny Island with its display at eye
level and by keeping a distance of 20 in (50 cm)
from the front.

• All cables are routed to the outside through the

underside of the enclosure. Therefore a minimum
clearance of 20 in (50 cm) must be observed here.

This manual is related to the following products: