7 failure categories, 8 warnings and error messages – SMA SI 4548-US User Manual
Page 208
20 Troubleshooting
SMA America, LLC
208
SI4548-6048-US-BE-en-20
Operating Manual
20.7 Failure Categories
The Sunny Island distinguishes between five different levels of errors, each requiring different user
interaction:
20.8 Warnings and Error Messages
The meanings of the warnings and errors displayed by the Sunny Island are described in the following
table:
E853
Sunny Island Charger #3 detected
E854
Sunny Island Charger #4 detected
E901
SOC recalibration started
E902
SOC recalibration stopped
E903
Derating started
E904
Derating stopped
E905
Preventive self-disconnection to protect the battery from deep discharge
Level
Designation
Display
Meaning
1
Warning
Warning
Warning, device continues to run. There is an explicit
information on the Home Screen that a warning was
recorded.
2
Malfunction 1 Malfunction
Failure that can only be detected during operation.
Device switches off. Device can be restarted
immediately (autostart).
3
Malfunction 2 Malfunction
Failure that can also be detected in standby mode.
Device switches off. The device can only be restarted
(autostart) once the system detects that the
malfunction has ended.
4
Error
Failure
Device error, device switches off. User interaction
required (troubleshooting, confirmation, manual
restart)
5
Device defect Defect
Device is defect. Device switches off and does not
switch on again. Permanent operation inhibition.
Device must be replaced.
Display no.
Description