SMA SI 4548-US User Manual
Page 167
SMA America, LLC
19 Parameter Lists
Operating Manual
SI4548-6048-US-BE-en-20
167
#222 Battery Charge Mode
03
BatVtgNom
Nominal battery
voltage
VRLA
48 V
FLA
48 V
NiCd
45.6 V
04
BatTmpMax
Max. battery
temperature
104°F to 122°F
(40°C to 50°C)
113°F
(45°C)
05
BatTmpStr
Battery start
temperature
following stop due
to overtemperature
32°F to 104°F
(0°C to 40°C)
"BatTmpMax"
104°F
(40°C)
06
BatWirRes
Power resistor of
the battery
connection in
mOhm
0 mOhm to
50 mOhm
07
BatFanTmpStr
Starting
temperature for the
"BatFan" function
104°F
(40°C)
No. Name
Description
Value
Explanation
Default
value
01
BatChrgCurMax Charging current
of the battery
10 A to 1,200 A
61 A
02
AptTmBoost
Absorption time for
normal charge
1 min to 600 min
VRLA
120 min
1 min to 600 min
FLA
90 min
1 min to 600 min
NiCd
300 min
03
AptTmFul
Absorption time for
full charge
1 h to 20 h
VRLA
5 h
1 h to 20 h
FLA
5 h
1 h to 20 h
NiCd
7 h
04
AptTmEqu
Absorption time for
equalization
charge
1 h to 48 h
10 h
05
CycTmFul
Cycle time of full
charge
1 day to 180 days
14 days
06
CycTmEqu
Equalization
charge cycle time
7 days to 365
days
180
days
No. Name
Description
Value
Explanation
Default
value