beautypg.com

SMA SI 4548-US User Manual

Page 167

background image

SMA America, LLC

19  Parameter Lists

Operating Manual

SI4548-6048-US-BE-en-20

167

#222 Battery Charge Mode

03

BatVtgNom

Nominal battery
voltage

VRLA

48 V

FLA

48 V

NiCd

45.6 V

04

BatTmpMax

Max. battery
temperature

104°F to 122°F
(40°C to 50°C)

113°F
(45°C)

05

BatTmpStr

Battery start
temperature
following stop due
to overtemperature

32°F to 104°F
(0°C to 40°C)
"BatTmpMax"

104°F
(40°C)

06

BatWirRes

Power resistor of
the battery
connection in
mOhm

0 mOhm to
50 mOhm

07

BatFanTmpStr

Starting
temperature for the
"BatFan" function

104°F
(40°C)

No. Name

Description

Value

Explanation

Default
value

01

BatChrgCurMax Charging current

of the battery

10 A to 1,200 A

61 A

02

AptTmBoost

Absorption time for
normal charge

1 min to 600 min

VRLA

120 min

1 min to 600 min

FLA

90 min

1 min to 600 min

NiCd

300 min

03

AptTmFul

Absorption time for
full charge

1 h to 20 h

VRLA

5 h

1 h to 20 h

FLA

5 h

1 h to 20 h

NiCd

7 h

04

AptTmEqu

Absorption time for
equalization
charge

1 h to 48 h

10 h

05

CycTmFul

Cycle time of full
charge

1 day to 180 days

14 days

06

CycTmEqu

Equalization
charge cycle time

7 days to 365
days

180
days

No. Name

Description

Value

Explanation

Default
value

This manual is related to the following products: