9 troubleshooting – SMA SI 4548-US User Manual
Page 218
20 Troubleshooting
SMA America, LLC
218
SI4548-6048-US-BE-en-20
Operating Manual
20.9 Troubleshooting
Answers are provided below for faults that may occur in practice:
Why does the Sunny Island not connect to the running generator?
• Is the AC disconnection unit on the generator ok?
• Has the power which is allowed to be fed back into the generator during the permissible time
been exceeded (parameter "233.14 GnRvTm")? If yes, "!" is displayed. Generator connection
is blocked for the set time. Set the parameter "540.02 GnAck" to Ackn.
• If the generator control relay (GnReq) is open has the generator been started manually
(parameter "234.07 GnStrMod")? Change the setting to autostart, if required.
• Is a GenMan used in the system?
– Check the return signal (DigIn)
– The generator can only be started manually using GenMan.
F932
3
Error message via SiCom: Different state of charge of the battery cells
F935
3
Error message via SiCom: Error in the generator
W936
1
Warning via SiCom: General
W937
1
Warning via SiCom: Battery overvoltage
W938
1
Warning via SiCom: Battery undervoltage
W939
1
Warning via SiCom: Battery overtemperature
W940
1
Warning via SiCom: Battery undertemperature
W941
1
Warning via SiCom: Battery overtemperature in charge mode
W942
1
Warning via SiCom: Battery undertemperature in charge mode
W943
1
Warning via SiCom: battery charging current too high
W944
1
Warning via SiCom: battery charging current in charge mode too high
W945
1
Warning via SiCom: error in the battery
W946
1
Warning via SiCom: short circuit
W947
1
Warning via SiCom: internal error in battery management
W948
1
Warning via SiCom: different state of charge of the battery cells
W951
1
Warning via SiCom: Generator
F952
3
Time for external battery management exceeded
W953
1
Time for external battery management exceeded
Display no.
Level
Description