beautypg.com

SMA SI 4548-US User Manual

Page 174

background image

19  Parameter Lists

SMA America, LLC

174

SI4548-6048-US-BE-en-20

Operating Manual

235# Generator Start

09

GnStpTmMin

Minimum stop time of
the generator

15 min

10

GnCoolTm

Cooling time of the
generator

5 min

11

GnErrStpTm

Stop time of generator
in case of errors

1 h

12

GnWarmTm

Warm-up time

60 sec

13

GnRvPwr

Generator reverse
power (active power)

100 W

14

GnRvTm

Permissible time for
reverse power/reverse
current

30 sec

15

GnCtlMod

Generator regulation

Cur

Current

Cur

CurFrq

Frequency

20

GnAlSns

AI sensitivity

Low

Low

Normal

Medium

Medium

Normal

Normal

High

High

41

GnCurCtlMod

Enable I-Loop in
generator mode

Droop (1)

Standard
generator
operation without
I-Loop

Droop (1)

CurCtl (2)

Current-controlled
generator
operation with
I-Loop

No. Name

Description

Value

Explanation

Default
value

01

GnAutoEna

Generator autostart

Off

Disable

On

On

Enable

02

GnAutoStr

Number of autostarts

3

03

GnSocTm1Str

SOC limit for switching
on generator for time 1

40%

No. Name

Description

Value

Explanation

Default
value

This manual is related to the following products: