19 Parameter Lists
SMA America, LLC
174
SI4548-6048-US-BE-en-20
Operating Manual
235# Generator Start
09
GnStpTmMin
Minimum stop time of
the generator
15 min
10
GnCoolTm
Cooling time of the
generator
5 min
11
GnErrStpTm
Stop time of generator
in case of errors
1 h
12
GnWarmTm
Warm-up time
60 sec
13
GnRvPwr
Generator reverse
power (active power)
100 W
14
GnRvTm
Permissible time for
reverse power/reverse
current
30 sec
15
GnCtlMod
Generator regulation
Cur
Current
Cur
CurFrq
Frequency
20
GnAlSns
AI sensitivity
Low
Low
Normal
Medium
Medium
Normal
Normal
High
High
41
GnCurCtlMod
Enable I-Loop in
generator mode
Droop (1)
Standard
generator
operation without
I-Loop
Droop (1)
CurCtl (2)
Current-controlled
generator
operation with
I-Loop
No. Name
Description
Value
Explanation
Default
value
01
GnAutoEna
Generator autostart
Off
Disable
On
On
Enable
02
GnAutoStr
Number of autostarts
3
03
GnSocTm1Str
SOC limit for switching
on generator for time 1
40%
No. Name
Description
Value
Explanation
Default
value