2 generator start options – SMA SI 4548-US User Manual
Page 119
SMA America, LLC
14 Connecting External Sources
Operating Manual
SI4548-6048-US-BE-en-20
119
14.1.2 Generator Start Options
The Sunny Island supports the following options for starting the generator which can be set in standby
mode with parameter "234.07 GnStrMod":
• Manual
• Autostart
Manual (Manual Generator Start)
This setting is for generators that do not have an electrical remote starting option and, for example,
are started using cable winches, cranks or similar.
In this case, the Sunny Island does not have the option of starting the generator. It only monitors the
generator input (AC2). If, while monitoring the input, the device detects that the generator voltage
and frequency are within the set limits (see Section 14.1.6 "Limits and Power Control", page 125),
the device is synchronized and connected following the warm-up time.
The following figure shows the wiring for a generator that cannot be started remotely:
The generator is also always switched off manually. The Sunny Island then automatically switches to
operation without generator.
Cable length and wire size
Use the same cable length and the same wire size when installing the Sunny Island inverters
with the generator.