beautypg.com

5 climatic conditions, 6 equipment, 7 torques – SMA SB 3600SE-10 User Manual

Page 61: 8 data storage capacity

background image

SB 3600SE-10

SB 5000SE-10

Maximum permissible fuse protection

32 A

32 A

Ground-fault monitoring

Insulation monitoring: R

iso

 > 400,000 Ω

Insulation monitoring: R

iso

 > 550,000 Ω

All-pole sensitive residual-current monitoring
unit

Available

Available

11.5 Climatic Conditions

Installation in accordance with IEC 60721-3-3, Class 3K5

Extended temperature range

0°C to + 40°C

Extended humidity range

5% to 95%

Extended air pressure range

79.5 kPa to 106 kPa

Transport in accordance with IEC 60721-3-2, Class 2K3

Temperature range

-30°C to +45°C

Relative humidity, non-condensing

5% to 95%

11.6 Equipment

DC connection

SUNCLIX DC connector

AC connection

Spring-cage terminal

Display

LC graphic display

Speedwire/Webconnect

As standard

Multifunction relay

Optional

11.7 Torques

Enclosure lid screws

6 Nm ± 0.5 Nm

Additional grounding terminal

9 Nm ± 0.5 Nm

SUNCLIX swivel nut

2.0 Nm

11.8 Data Storage Capacity

Energy yields in the course of the day

63 days

Daily yields

30 years

Event messages for users

250 events

Event messages for installers

250 events

11 Technical Data