2 restarting the self-test, Restarting the self-test – SMA SB 3600SE-10 User Manual

Page 43

background image

Example: Display messages for overvoltage test

- Name of the test: Autotest (59.S1) 240.00V
- Disconnection value: Valore di soglia con 230.00V
- Normative value: Va. taratura 253.00V
- Disconnection time: Tempo die intervento 0.02 s
- Current line voltage: Tensione di rete Val.eff.: 229.80V

7.4.2

Restarting the Self-Test

1. Disconnect the circuit breaker and secure it against reconnection.
2. If the multi-function relay is used, switch off the load supply voltage, if necessary.
3. Turn the DC load-break switch towards OFF until it snaps into place at position O.
4. Wait five minutes.
5. Turn the DC load-break switch towards ON until it snaps into place at position I.
6. Recommission the inverter.

☑ The inverter is back in the start-up phase and you can start the self-test (see Section 7.4.1,

page 41).

7 Commissioning

SMA Solar Technology AG

Operating Manual

43

SB36-50SE-BE-en-11