5 Mounting
5.1 Requirements for Mounting
Requirements for the mounting location:
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the inverter and the Battery Pack in areas containing highly flammable
materials or gases.
• Do not mount the inverter or the Battery Pack in a potentially explosive atmosphere.
• Do not mount the inverter or the Battery Pack in areas of high humidity (see Section 11
☐ The mounting location must not be outdoors.
☐ Mounting on a pillar or top-hat rail is not permitted.
☐ Mounting of the inverter and Battery Pack must take place using the supplied wall mounting
bracket only.
☐ The mounting location must be inaccessible to children.
☐ A solid, flat support surface, e.g. concrete or masonry, must be available for mounting. When
mounted on drywall or similar materials, the inverter emits audible vibrations during operation
which could be perceived as annoying.
☐ The mounting location must be suitable for the weight and dimensions of the inverter and the
Battery Pack (see Section 11 "Technical Data", page 57).
☐ The mounting location must not be exposed to direct solar irradiation.
☐ Climatic conditions must be met (see Section 11 "Technical Data", page 57).
☐ To ensure optimal operation of the inverter and the Battery Pack, the ambient temperature
should be between +15°C and +30°C.
☐ The mounting location should be clear and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.