Super Systems 20Q User Manual
Page 95
Gr.dFGr.dFGr.dFGr.dFGr.dF
91
Run time group 8 [r.Hxx]
Run time group 8 [r.Hxx]
Run time group 8 [r.Hxx]
Run time group 8 [r.Hxx]
Run time group 8 [r.Hxx]
FEEDBACK POTENTIOMETER ADJUSTMENT
NOTE
NOTE
NOTE
NOTE
NOTE: The run time group 8 will be displayed only if the
instrument is in MANUAL mode.
- Feedback potentiometer adjustment
- Feedback potentiometer adjustment
- Feedback potentiometer adjustment
- Feedback potentiometer adjustment
- Feedback potentiometer adjustment
enabling - [r.H01]
enabling - [r.H01]
enabling - [r.H01]
enabling - [r.H01]
enabling - [r.H01]
This parameter is available only when close loop servomotor
output or open loop servomotor output with valve position
indication is configured.
Range: OFF = this selection disables the feedback potentiom-
eter calibration and the instrument will come
back to the first display of the run time group 8.
On
= this selection starts the feedback potentiometer
calibration.
NOTE
NOTE
NOTE
NOTE
NOTE: No time out will be applied during
feedback potentiometer calibration procedure.
- Servomotor low limit positioning -
- Servomotor low limit positioning -
- Servomotor low limit positioning -
- Servomotor low limit positioning -
- Servomotor low limit positioning -
[r.H02]
[r.H02]
[r.H02]
[r.H02]
[r.H02]
This parameter is available only when feedback potentiometer
calibration enabling [r.H01] is equal to On.
Range: 0.0% to 100.0%
The middle display will show the valve position as a percentage
of the full input span.
By and push-button it is possible to modify the valve
position.
When the desired initial position has been reached, push the
FUNC push-button.
- Feedback low limit calibration - [r.H03]
- Feedback low limit calibration - [r.H03]
- Feedback low limit calibration - [r.H03]
- Feedback low limit calibration - [r.H03]
- Feedback low limit calibration - [r.H03]
This parameter is available only when feedback potentiometer
calibration enabling [r.H01] is equal to On.
Range: OFF = To skip calibration and hold the previous value
select OFF and then push FUNC
On
= To memorize the current position as feedback
low limit calibration select “On” and then push
FUNC
Gr.8Gr.8Gr.8Gr.8Gr.8
mkc-ssi.pmd
06/07/2004, 12.19
91