Super Systems 20Q User Manual
Page 40
CnF. 1CnF. 1CnF. 1CnF. 1CnF. 1
36
NOTE
NOTE
NOTE
NOTE
NOTE: The parameter “L.r.O.ñ” (local/remote set point operative
mode [C.d16]) will be forced to “n.ALG” if “A.In.F” (auxiliary input
function [C.d09]) is equal to “bIAS” and “A.I.Añ” (auxiliary input
activation mode [C.d14]) is equal to “Cnd.A”.
- Auxiliary input safety condition -
- Auxiliary input safety condition -
- Auxiliary input safety condition -
- Auxiliary input safety condition -
- Auxiliary input safety condition -
[C.d15]
[C.d15]
[C.d15]
[C.d15]
[C.d15]
This parameter is available only when auxiliary input is configured
and "A.i.Añ" [C.d14] is equal to "norñ".
Range: nonE = when the auxiliary input is out of range, the
instrument operates as in presence of the min or
max auxiliary input value.
Cnd.A = when the auxiliary input is out of range, the
control output goes to safety value “SF.UL”
(output safety value [C.G08]).
If servomotor open loop control drive is
configured the “Safety value” "SF.UL" [C.G08]
has no effect and the instrument operates in
accordance with “SF.Cn” (Output safety
condition [C.G07]) parameter setting.
NOTE:
NOTE:
NOTE:
NOTE:
NOTE: The “SF.Cn” (Output safety condition” [C.G07]) has the
priority on “A.I.Sc” (auxiliary input safety condition [C.d15]).
- Local/remote set point operative mode
- Local/remote set point operative mode
- Local/remote set point operative mode
- Local/remote set point operative mode
- Local/remote set point operative mode
- [C.d16]
- [C.d16]
- [C.d16]
- [C.d16]
- [C.d16]
This parameter is available only when auxiliary input is configured
Range: ALG = when the transfer from remote to local set point
is performed, the local set point value will be
aligned to last remote set point value.
n.ALG = when the transfer from remote to local set point
is performed, the local set point value will not
be changed (The programmed ramps Grd1
[r.E14] and Grd2 [r.E15] may be activated).
NOTES
NOTES
NOTES
NOTES
NOTES:
1) The selected local set point will be changed even if it is
software protected.
2) The parameter is forced to “n.ALG” if “A.In.F” (auxiliary input
function [C.d09]) is equal to “bIAS” and “A.I.Añ” (auxiliary input
activation mode [C.d14]) is equal to “Cnd.A”
General note on configuration group 1
General note on configuration group 1
General note on configuration group 1
General note on configuration group 1
General note on configuration group 1
Exiting from the configuration group 1 the instrument verifies
automatically the programmed span for the linear input.
If it is wrong, the device will show:
mkc-ssi.pmd
06/07/2004, 12.19
36