Super Systems 20Q User Manual

Page 37

background image

CnF. 1CnF. 1CnF. 1CnF. 1CnF. 1

33

- Read-out- full scale value - [C.d06]

- Read-out- full scale value - [C.d06]

- Read-out- full scale value - [C.d06]

- Read-out- full scale value - [C.d06]

- Read-out- full scale value - [C.d06]

Ranges: - from -1999 to 9999 for linear input (Input range 31 to

38),

- from 0 to 9999 for linear input with square root

extraction,

- from "ñ.In.L" (read-out- initial scale value [C.d05]) to full

range value for TC/RTD input.

NOTES

NOTES

NOTES

NOTES

NOTES:
1) Changing the value of this parameter, the "brG.H" (bargraph -

full scale value [C.I04]) and "rH" (set point high limit [r.E13])
parameters will be realigned to it.

2) The programmed input span, in absolute value, must be

greater than:
300 °C or 550 °F for TC inputs
100°C or 200 °F for RTD inputs
100 digits for linear inputs.

2) When the square root extraction is enabled the "ñ.In.L" (read-

out - initial scale value [C.d05]), "ñ.In.H" (read-out - full scale
value [C.d06]), "brG.L" (bargraph - initial scale value [C.I03]),
"brG.H" (bargraph - full scale value [C.I04]) and "SS.th"
(threshold to enable the soft start [C.I09]) parameter values
must be positive or equal to zero.
Enabling the square root extraction the instrument verify the
actual value of the "ñ.In.L", "ñ.In.H", "brG.L", "brG.H" and
"SS.th" parameters and force to zero the eventual negative
values.

- Read-out- initial scale value - [C.d05]

Read-out- initial scale value - [C.d05]

Read-out- initial scale value - [C.d05]

Read-out- initial scale value - [C.d05]

Read-out- initial scale value - [C.d05]

Ranges: - from -1999 to 9999 for linear input (Input range 31 to

38),

- from 0 to 9999 for linear input with square root

extraction,

- from initial range value to "ñ.In.H" (read-out- full scale

value C.d06]) for TC/RTD input

NOTE

NOTE

NOTE

NOTE

NOTE: Changing the value of this parameter, the "brG.L"
(bargraph - initial scale value [C.I03]) and "rL" (set point low limit
[r.E12]) parameters will be realigned to it.
If a linear input is selected, also the “SS.th” (threshold for soft
start [C.I09]) will be realigned to it.

mkc-ssi.pmd

06/07/2004, 12.19

33