beautypg.com

Super Systems 20Q User Manual

Page 9

background image

5

Shield

+

_

TX

3

1

11

7

A.3) LINEAR INPUT

A.3) LINEAR INPUT

A.3) LINEAR INPUT

A.3) LINEAR INPUT

A.3) LINEAR INPUT

Fig. 6 mA, mV AND V INPUTS WIRING

NOTES

NOTES

NOTES

NOTES

NOTES:
1) Don’t run input wires together with power cables.
2) Pay attention to the line resistance; a high line resistance may

cause measurement errors.

3) When shielded cable is used, it should be grounded at one

side only to avoid ground loop currents.

4) The input impedance is equal to:

< 5

for 20 mA input

> 1 M

for 60 mV input

> 200 k

for 5 V input

> 400 k

for 10 V input

A.4) 2, 3 AND 4-WIRE TRANSMITTER INPUT

A.4) 2, 3 AND 4-WIRE TRANSMITTER INPUT

A.4) 2, 3 AND 4-WIRE TRANSMITTER INPUT

A.4) 2, 3 AND 4-WIRE TRANSMITTER INPUT

A.4) 2, 3 AND 4-WIRE TRANSMITTER INPUT

Fig. 7.A INPUTS WIRING FOR 2-WIRE TRANSMITTER

Shield

_

+

mA,

mV

or

V

3

1

+

_

G

mA
mV

or

V

1

3

mkc-ssi.pmd

06/07/2004, 12.19

5