Super Systems 20Q User Manual
Page 36
CnF. 1CnF. 1CnF. 1CnF. 1CnF. 1
32
33 = Linear
From
0 to
5
V
34 = Linear
From
1 to
5
V
35 = Linear
From
0 to
10
V
36 = Linear
From
2 to
10
V
37 = Linear
From
0 to
60 mV
38 = Linear
From
12 to
60 mV
* For these ranges it is possible to select a read-out with one
decimal figure but the instrument could not display a measure
lower than -199.9 or higher than 999.9 and the input range
will be limited by it.
NOTES
NOTES
NOTES
NOTES
NOTES:
1) When a linear input is selected, the instrument set automati-
cally the "readout initial scale value" [C.d05] equal to 0 and
the "readout final scale value" [C.d06] equal to 4000
2) When input type has been changed, the instrument
automatically forces:
- the "ñ.In.L" [C.d05], "SS.th" [C.I09] and "brG.L" [C.I03]
parameters to the new initial scale value,
- the "ñ.In.H" [C.d06] and "brG.H" [C.I04] parameter to the new
final scale value and
- the "ñ.In.d" [C.d03] parameter to "no decimal figure".
- Decimal point position - [C.d03]
- Decimal point position - [C.d03]
- Decimal point position - [C.d03]
- Decimal point position - [C.d03]
- Decimal point position - [C.d03]
Ranges:
----.
= no decimal figure
---.-
= one decimal figure
--.--
= two decimal figures
-.---
= three decimal figures
NOTES
NOTES
NOTES
NOTES
NOTES:
1) For main input type 1 to 6, 15 and 30 only the "no decimal
figure" and "one decimal figure" are selectable, the input
range is limited within -199.9 and 999.9 and it acts as an
input type changement.
2) For main input type 7 to 14 and 16 to 29 this parameter is not
available.
3) For linear input types (from 31 to 38) all positions are available.
- Square root extraction for main input
- Square root extraction for main input
- Square root extraction for main input
- Square root extraction for main input
- Square root extraction for main input
- [C.d04]
- [C.d04]
- [C.d04]
- [C.d04]
- [C.d04]
Ranges: dIS = square root extraction disabled
Enb = square root extraction enabled
NOTES
NOTES
NOTES
NOTES
NOTES:
1) This parameter is available only for main input type 31 to 38.