CnF. 4CnF. 4CnF. 4CnF. 4CnF. 4
50
- Condition for output safety value -
- Condition for output safety value -
- Condition for output safety value -
- Condition for output safety value -
- Condition for output safety value -
[C.G07]
[C.G07]
[C.G07]
[C.G07]
[C.G07]
This parameter will be available only when at least one control
output is configured.
Ranges:
- When no output is configured as open loop servomotor control,
"SF.Cn" can be set as follows:
Std.
= No safety value (“standard setting” see chapter
ERROR MESSAGES).
Ov.Un = Safety value applied when the instrument detect
an overrange or underrange condition of the
main input.
OvEr = Safety value applied when the instrument detect
an overrange condition of the main input.
Undr = Safety value applied when the instrument detect
an underrange condition of the main input.
- When the open loop servomotor control is configured, "SF.Cn"
can be set as follows:
Std.
= No safety value (“standard setting” see chapter
ERROR MESSAGES).
Cnd.A = When the instrument detects an overrange or
underrange condition of the main input, the
servomotor is driven to its high limit position.
Cnd.b = When the instrument detects an overrange or
underrange condition of the main input, the
servomotor is driven to its low limit position.
Cnd.C = When the instrument detects an overrange or
underrange condition of the main input, the
action on servomotor is the complement of
“standard” setting.
- Output safety value - [C.G08]
- Output safety value - [C.G08]
- Output safety value - [C.G08]
- Output safety value - [C.G08]
- Output safety value - [C.G08]
This parameter will be available only when "SF.Cn" [C.G07] is
equal to “Ov.Un”, “OvEr” or “Undr”or the parameter “A.I.Sc”
("Auxiliary input safety condition" [C.d15]) is equal to “Cnd.A”
Range:
- from 0.0 to 100.0 if device is configured with one control
output;
- from -100.0 to 100.0 if device is configured with two control
outputs (split range excluded).