Super Systems 20Q User Manual
Page 111
107
Output type
Output type
Output type
Output type
Output type: Isolated output programmable as
- 0-20 mA
- 4-20 mA.
Scaling
Scaling
Scaling
Scaling
Scaling: programmable from -1999 to 9999.
Maximum load
Maximum load
Maximum load
Maximum load
Maximum load: 600
Ω.
A c c u r a c y
A c c u r a c y
A c c u r a c y
A c c u r a c y
A c c u r a c y :
- 0.1 % when it is used as control output
- 0.05 % when it is used as analog retransmission. Note
Note
Note
Note
Note: a too
little range scaling can deteriorate the output accuracy.
Filter
Filter
Filter
Filter
Filter: It is possible to apply a first order digital filter on the
retransmitted value.
The time constant of the filter may be programmed within 0 and
8 s.
Additional 5 + 5 outputs (OUT10 to 19)
Additional 5 + 5 outputs (OUT10 to 19)
Additional 5 + 5 outputs (OUT10 to 19)
Additional 5 + 5 outputs (OUT10 to 19)
Additional 5 + 5 outputs (OUT10 to 19)
Function
Function
Function
Function
Function: singularly settable from keyboard or serial link.
Type
Type
Type
Type
Type: Relay .
Relay type
Relay type
Relay type
Relay type
Relay type: SPST
Contact rating
Contact rating
Contact rating
Contact rating
Contact rating: 0.5 A @ 250 V on resistive load.
Note
Note
Note
Note
Note: The commons of the out 10 to 14 connected together
with the terminal 66 while the commons of the output 15 to 19
are connected with terminal 55.
ALARMS
ALARMS
ALARMS
ALARMS
ALARMS
Alarm action
Alarm action
Alarm action
Alarm action
Alarm action: direct or reverse function programmable.
Alarm functions
Alarm functions
Alarm functions
Alarm functions
Alarm functions: each alarm can be configured as process
alarm, band alarm, deviation alarm, alarm on main or secondary
control output value.
Alarm reset
Alarm reset
Alarm reset
Alarm reset
Alarm reset: automatic or manual reset programmable on
each alarm.
Alarm masking
Alarm masking
Alarm masking
Alarm masking
Alarm masking: each alarm can be configured as masked
alarm or standard alarm.
This function allows you to delete false indication at instrument
start up and after a set point change.
Process alarm
Process alarm
Process alarm
Process alarm
Process alarm:
Operative mode
Operative mode
Operative mode
Operative mode
Operative mode: Minimum or maximum programmable.
Threshold
Threshold
Threshold
Threshold
Threshold: programmable in engineering unit within the input
range.
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Hysteresis: programmable in engineering units from 1 to 200
digits.
Band alarm
Band alarm
Band alarm
Band alarm
Band alarm
Operative mode
Operative mode
Operative mode
Operative mode
Operative mode: Inside or outside programmable.
Threshold
Threshold
Threshold
Threshold
Threshold: two thresholds programmable:
- Low - from 0 to -1000 digits.
- High - from 0 to +1000 digits.
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Hysteresis: programmable in engineering units from 1 to 200
digits.