Super Systems 20Q User Manual
Page 52
CnF. 3CnF. 3CnF. 3CnF. 3CnF. 3
48
CONFIGURATION GROUP 4 [C.Gxx]
CONFIGURATION GROUP 4 [C.Gxx]
CONFIGURATION GROUP 4 [C.Gxx]
CONFIGURATION GROUP 4 [C.Gxx]
CONFIGURATION GROUP 4 [C.Gxx]
AUXILIARY CONTROL CONFIGURATION
- Smart function - [C.G01]
- Smart function - [C.G01]
- Smart function - [C.G01]
- Smart function - [C.G01]
- Smart function - [C.G01]
This parameter will be available only when at least one control
output is configured
Range: dIS
= Smart function disabled
Enb
= Smart function may be enabled
- Control action type - [C.G02]
- Control action type - [C.G02]
- Control action type - [C.G02]
- Control action type - [C.G02]
- Control action type - [C.G02]
This parameter will be available only when at least one control
output is configured
Range: Pid
= The process is controlled by PID actions
Pi
= The process is controlled by PI actions
- Manual function - [C.G03]
- Manual function - [C.G03]
- Manual function - [C.G03]
- Manual function - [C.G03]
- Manual function - [C.G03]
This parameter will be available only when at least one control
output is configured
Range: dIS
= Manual function disabled
Enb
= Manual function may be enabled
- Output value for AUTO to MAN transfer
- Output value for AUTO to MAN transfer
- Output value for AUTO to MAN transfer
- Output value for AUTO to MAN transfer
- Output value for AUTO to MAN transfer
- [C.G04]
- [C.G04]
- [C.G04]
- [C.G04]
- [C.G04]
This parameter will be available only when at least one control
output is configured and manual function is enabled (“ñAn.F”
[C.G03] = “Enb”)
Range: - from 0.0 to 100.0 % of the output span if device is
configured with only one control output
- from -100.0 to 100.0 of the output span if device is
configured with two control outputs (split range
excluded).
Above the value 100.0 the display shows “buñ.” meaning that the
transfer from AUTO to MANUAL is bumpless (the instrument set
for MANUAL mode the same power output used in AUTO mode)
CnF.4CnF.4CnF.4CnF.4CnF.4
mkc-ssi.pmd
06/07/2004, 12.19
48