REMKO WPM-Smart-Control-Manual for specialists-WKF-120 User Manual

Page 89

background image

Designation

Input

Output

Signal

Description

A11.1

X

Changeover valve 2nd WE Smart BVT

A12.1

X

Not connected

A13.1

X

2nd mixed heating cycle pump (230V) switched

A14.1

X

Changeover valve / pump cooling (230V)

A20.1

X

1st mixed heating cycle mixer open (230V)

A21.1

X

1st mixed heating cycle mixer closed (230V)

A22.1

X

Bypass valve indoor unit closed (230V)

A23.1

X

Bypass valve indoor unit open (230V)

A24.1

X

2nd mixed heating cycle mixer open (230V)

A25.1

X

2nd mixed heating cycle mixer closed (230V)

A30.1

X

Non functional

A31.1

X

Non functional

A32.1

X

Enable 2nd WE booster heating or boiler

A33.1

X

Non functional

A34.1

X

Alarm codes

A40.1

X

Speed setting solar pump PWM

A41.1

X

Speed setting 1st mixed heating cycle (0-10V)

A42.1

X

Speed setting unmixed heating cycle (0-10V)

A43.1

X

Speed setting primary pump M 0-10V

A44.1

X

Not connected

A45.1

X

Not connected

A46.1

X

Pump second mixed heating cycle

MI

Non functional

MO

CLK

nSS

GND

OT 1 (2x)

Non functional

OT 2 (2x)

Non functional

B1, A1

+12 Volt,

GND

Operat. module SMT 1 and communic. I/0 module 2

B2 / A2

Communication Com-Kit 1

B3 / A2

Non functional

RC.1

RC coding resistance WKF 120/180 Duo

89