Domestic hot-water heating

Optionally, you can activate or deactivate the

"Domestic hot-water heating" function. Activate

Domestic hot-water heating if domestic water has

to be heated for washing or showering (select with

the rotary knob and confirm with "OK"). When this

function is activated, the associated parameters

are then queried. Pay attention to information on

the display.

Fig. 41: Domestic hot-water heating

Press "Next".

Reheating

Desired charging temperature for the hot water

storage tank.

Set temperature to which conventional reheating

should heat the storage tank to ensure comfort. If

there is a solar yield, the storage tank can become

substantially warmer. The maximum temperature

for solar charging can be modified under Settings/

Solar/Storage tank.

For efficiency reasons, the lowest possible set tem-

perature should be selected. If the available quan-

tity of hot water is insufficient, the value should be

increased. Pay attention to the maximum tempera-

ture of the heat pump.

Select the storage tank set temperature with the

rotary knob and confirm with "OK".

Fig. 42: Reheating

Menu item

Parameter

Factory setting

Storage tank

set temp.

40°C - 65°C

Factory recom-

mendation

45°C

Press "Next".