Fig. 60: Setting the standard inlet temperature
Fig. 61: Set the standard outside temperature
Fixed-value-control heating cycle mode
Specify the set temperature for fixed value control
(select with the rotary knob and confirm with "OK").
The heating cycle is kept permanently at this tem-
perature in fixed value control.
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat pump
to operate inefficiently.
After activating the 2nd mixed heating cycle,
the 3rd mixed heating cycle is enabled.
3rd mixed heating cycle (only WKF Duo)
Activate if a heating cycle with radiators is
installed. (select with the rotary knob and confirm
with "OK")
Fig. 62: Activate 3rd mixed heating cycle
Menu item
Parameter
Factory setting
3rd mixed
heating
cycle
Deactivated
Deactivated
Activated
Press "Next".
Setting heating cycle mode
This is where you can select between the different
heating cycle modes. The choice is between con-
trol according to the set "Heating curve" and
"Fixed value control" (select with the rotary knob
and confirm with "OK").
Menu item
Parameter
Factory setting
Heating
cycle mode
for HK active
Heating curve
According
to design
Fixed value
10°C - 40°C
Press "Next".
Heating-curve heating cycle mode
The heating curve can be adjusted in three points,
according to the structure and location-related con-
ditions of the building:
Base point:
The base point corresponds to the minimum set
temperature of the heating water at an outside
temperature of 20°C. If the heating is too cold at
relatively high outside temperatures (trans-sea-
sonal period), the base point should be set higher.