Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-120 User Manual
Page 42
Fig. 70: Setting the standard inlet temperature
Fig. 71: Set the standard outside temperature
System separation
Activation if a mixed heating cycle is separated by
a heat exchanger.
To control a separate heating cycle pump with
system separation by means of a heat exchanger,
the function "System separation FBH" must be
activated. (select with the rotary knob and confirm
with "OK")
Fig. 72: Activating the system separation
Menu item
Parameter
Factory setting
System sep-
aration FBH
Deactivated
Deactivated
Activated
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat pump
to operate inefficiently.
After activating the system separation it is possible
to select a setpoint increase, in order to balance
the heat losses with a heat exchanger.
Fig. 73: Adjustment of the setpoint temperature
Menu item
Parameter
Factory setting
Setpoint
temperature
0 - 10
5.0 K
REMKO Smart WP MANAGER