Setting the heating curve:

- Activate the base point with the right softkey, set

with the rotary knob and conform with the right

softkey.

Fig. 49: Setting the base point

- The standard inlet temperature and the outside

temperature are set using the same procedure.

Fig. 50: Setting the standard inlet temperature

Fig. 51: Setting the outside temperature

Fixed-value-control heating cycle mode

Specify the set temperature for fixed value control

(select with the rotary knob and confirm with "OK").

The heating cycle is kept permanently at this tem-

perature in fixed value control.

Press "Next".

1st mixed heating cycle

Activate if a heating cycle with radiators is

installed. (select with the rotary knob and confirm

with "OK")

Fig. 52: Activate 1st mixed heating cycle

Menu item

Parameter

Factory setting

1st mixed

heating

cycle

Deactivated

Deactivated

Activated

Press "Next".

Setting heating cycle mode

This is where you can select between the different

heating cycle modes. The choice is between con-

trol according to the set "Heating curve" and

"Fixed value control" (select with the rotary knob

and confirm with "OK").

Menu item

Parameter

Factory setting

Heating

cycle mode

for HK active

Heating curve

According

to design

Fixed value

10°C - 40°C

Press "Next".

Heating-curve heating cycle mode

The heating curve can be adjusted in three points,

according to the structure and location-related con-

ditions of the building:

Base point:

The base point corresponds to the minimum set

temperature of the heating water at an outside

temperature of 20°C. If the heating is too cold at

relatively high outside temperatures (trans-sea-

sonal period), the base point should be set higher.

REMKO Smart WP MANAGER