beautypg.com

Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-120 User Manual

Page 56

background image

Menu item

Parameter

Factory setting

WKF

WKF

Duo

Activate heat pump

Activated / Deactivated

Activated

X

X

Operating mode

Monoenergetic/

bivalent alternative

Monoenergetic

X

X

Dom. hot water heating

Activated / Deactivated

Activated

X

X

Storage tank set temp.

"40°C - 65°C"

45°C

X

X

Hot water circulation

Activated / Deactivated

Deactivated

X

X

Circulation type

Impulse

Deactivated

X

X

Circulation running time

1 min - 15 mins

5 mins

X

X

Disable switch-on

1 min - 15 mins

5 mins

X

X

Circulation type

Temperature

Deactivated

X

X

Circulation set temp

"25°C - 65°C"

35 °C

X

X

Unmixed heating cycle

Activated / Deactivated

Deactivated

X

X

Heating cycle mode

Heating curve

Deactivated

X

X

Heating-curve base point

"15°C - 35°C"

30 °C

X

X

Standard inlet temperature "40°C - 90°C"

55 °C

X

X

Standard outside temp.

"0°C - 20°C"

20 °C

X

X

1st mixed heating cycle

Activated / Deactivated

Deactivated

X

X

Heating cycle mode

Heating curve

Deactivated

X

X

Heating-curve base point

"15°C - 25°C"

20 °C

X

X

Standard inlet temperature "28°C - 90°C"

35 °C

X

X

Standard outside temp.

"0°C - 20°C"

20 °C

X

X

Heating cycle mode

Heating curve

Deactivated

X

X

Heating-curve base point

"15°C - 25°C"

20 °C

X

X

Standard inlet temperature "28°C - 90°C"

35 °C

X

X

Standard outside temp.

"0°C - 20°C"

20 °C

X

X

3rd mixed heating cycle

Activated / Deactivated

Deactivated

-

X

Heating cycle mode

Heating curve

Deactivated

-

X

Heating-curve base point

"15°C - 25°C"

20 °C

-

X

Standard inlet temperature "28°C - 90°C"

35 °C

-

X

Standard outside temp.

"0°C - 20°C"

20 °C

-

X

REMKO Smart WP MANAGER

56