Standard inlet temperature:
the standard inlet temperature corresponds to the
set temperature of the heating water at the
standard outside temperature in the building loca-
tion. If the heating is not warm enough at low out-
side temperatures, the standard inlet temperature
should be increased.
Standard outside temperature:
the standard outside temperature is dependent on
the regional location of the building. Please consult
your heating installer.
2
1
4
3
Fig. 63: Heating curve adjustment
1: Temperature of the heating water in °C
2: Inlet temperature heating curve
3: Return flow heating curve
4: Outside temperature in °C
Setting the heating curve:
- Activate the base point with the right softkey, set
with the rotary knob and conform with the right
softkey.
Fig. 64: Setting the base point
- The standard inlet temperature and the outside
temperature are set using the same procedure.
Fig. 65: Setting the standard inlet temperature
Fig. 66: Set the standard outside temperature
Fixed-value-control heating cycle mode
Specify the set temperature for fixed value control
(select with the rotary knob and confirm with "OK").
The heating cycle is kept permanently at this tem-
perature in fixed value control.
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat pump
to operate inefficiently.
After activating the 3rd mixed heating cycle,
the 4th mixed heating cycle is enabled.