beautypg.com

Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-120 User Manual

Page 40

background image

Standard inlet temperature:

the standard inlet temperature corresponds to the

set temperature of the heating water at the

standard outside temperature in the building loca-

tion. If the heating is not warm enough at low out-

side temperatures, the standard inlet temperature

should be increased.

Standard outside temperature:

the standard outside temperature is dependent on

the regional location of the building. Please consult

your heating installer.

2

1

4

3

Fig. 63: Heating curve adjustment

1: Temperature of the heating water in °C

2: Inlet temperature heating curve

3: Return flow heating curve

4: Outside temperature in °C

Setting the heating curve:

- Activate the base point with the right softkey, set

with the rotary knob and conform with the right

softkey.

Fig. 64: Setting the base point

- The standard inlet temperature and the outside

temperature are set using the same procedure.

Fig. 65: Setting the standard inlet temperature

Fig. 66: Set the standard outside temperature

Fixed-value-control heating cycle mode

Specify the set temperature for fixed value control

(select with the rotary knob and confirm with "OK").

The heating cycle is kept permanently at this tem-

perature in fixed value control.

For optimal configuration of the heating curve

parameters, the heating load calculation and/or

energy consumption must be taken into account.

Differences between the installed parameters and

the design of the actual building can cause the

heat pump to run inefficiently.

Operating the heating cycle with a fixed value is

not recommended, as it will cause the heat pump

to operate inefficiently.

After activating the 3rd mixed heating cycle,

the 4th mixed heating cycle is enabled.

REMKO Smart WP MANAGER

40